Array-level calculations aggregate individual outputs, apply AC losses in sequence—auxiliary load deductions, losses, and AC collection system losses—then aggregate array outputs to the block level. Each array is calculated independently using repeater counts at both the inverter and array levels.
Each array may contain multiple inverters (with repeater counts). Because all inverters in an array operate at the same AC voltage and frequency, they are connected in parallel upstream of the MV transformer and their powers add directly. The total array-level AC power is:PAC,array=inverters∑PAC,inv×nrep,invThis aggregated power is the input to AC degradation (see Degradation Losses (AC Applied)), which produces PAC,deg, accounting for both standard degradation and losses.
Auxiliary loads are constant power deductions subtracted from the degraded AC power before transformer losses. The tracker motor load (Ltrack) is aggregated from per-DC-field “Tracker Actuator Load” inputs (specified in MWh/MWp/year), scaled by each field’s DC capacity and repeater counts on DC fields and inverters; it is zero for fixed-tilt systems.Paux=PAC,deg−LDAS−Lcool−LtrackBefore the , all auxiliary loads are zero (the system is not yet commissioned). After energization:
DAS load is applied regardless of whether the array is producing power.
Cooling and tracker motor loads are applied only when the total inverter output is positive (PAC,array>0); otherwise they are zero.
overrides all of the above: when triggered, all three auxiliary loads are set to zero (see Inverter Operating Regions for trigger conditions).
If an MV transformer is defined for the array, the Transformer Loss Model is applied to Paux:PMV=Paux−LMV,transwhere LMV,trans is computed from the quadratic loss equation using PMV,rated, LNL,MV, and LFL,MV. When Nighttime Disconnect is enabled and triggered, the transformer no-load loss is set to zero, eliminating standby core losses.If no MV transformer is defined, there is no loss: LMV,trans=0 and PMV=Paux.
AC collection losses represent resistive losses in the medium-voltage cabling between the MV transformer and the plant-level collection point. The input loss percentage fcoll is converted to a fraction before use.Versions 3–11 (Flat Percentage Model):During daytime operation (PMV>0):Lcoll=PMV×fcollPcoll=PMV−Lcoll=PMV×(1−fcoll)During nighttime operation (PMV≤0), power flows in reverse—the grid supplies current through the collection system to keep transformers energized. The collection line losses compound: the grid must supply extra power to cover the losses, and that extra power itself incurs additional losses. The effective loss fraction becomes (1+fcoll)2−1≈2fcoll for small fcoll:Lcoll=∣PMV∣×[(1+fcoll)2−1]≥0Pcoll=PMV−Lcoll=PMV×(1+fcoll)2≤0Version 12+ (Quadratic Model):Loss scales quadratically with power flow, reflecting the I²R characteristic of conductor losses:Lcoll=PAC,rated,arrayPMV2×fcollwhere PAC,rated,array is the total inverter rated capacity for the array (scaled from kVA to VA):PAC,rated,array=inverters∑PAC,rated×nrep,invThe collection output is:Pcoll=PMV−Lcoll